High Voltage Tester HVT-70/50 perform DC high-voltage testing of power cables (IEC 60502-2) up to 70 kV, power cables accessories (IEC 61442) as well as AC high-voltage testing, up to 50 kV at 50 Hz, of switchgear, reclosers, dielectric insulators, highvoltage dischargers (arresters), busbars and other dielectric materials with relatively low electric capacitance.
| Parameter | Value | 
| Supply voltage single-phase alternating current, V | 220 ± 22 | 
| Frequency, Hz | 50 ± 2 | 
| Maximum power consumption, kVA, max | 3 | 
| Highest output voltage, kV: | |
| – AC | 50 | 
| – DC | 70 | 
| Highest output current, mA: | |
| – on AC voltage | 44 | 
| – on DC voltage | 14 | 
| Reduced voltage error, %, max: | |
| – AC voltage from 2 kV to 50 kV | ± 3 | 
| – DC voltage from 2 kV to 70 kV | ± 3 | 
| Reduced current error, %, max: | |
| – AC from 1,0 mA to 45,0 mA | ± 3 | 
| – DC from 0,5 mA to 14,5 mA | ± 3 | 
| Maximum current threshold on the high-voltage side, mA, max: | |
| – AC voltage | 45 | 
| – DC voltage | 14,5 | 
| Control Unit dimensions, mm, max | 266 × 240 × 354 | 
| Control Unit Weight, kg, max | 13 | 
| High Voltage Unit dimensions, mm, max | 360×310×500 | 
| High Voltage Unit weight, kg, max | 33 | 
| lifespan, years, avg | 10 | 
| Component | Quantity | 
| Control Unit | 1 | 
| High Voltage Unit | 1 | 
| Power cable (length 4 m, cross-section 3×0,75 mm2) | 1 | 
| Grounding cable (length 4 m, cross-section 4 mm2) | 2 | 
| High Voltage cable (length 4 m) | 1 | 
| Safety fuse VP2 –1, 1.0 А | 2 | 
| Safety fuse VP3 –1, 10.0 А | 2 | 
| Documentation | |
| User’s manual | 1 | 
| Metrological certification “Харьковстандартметрология” | Optional | 

hvt-70-50-safenergy-i-din-moxa-ti-vit-nam