MRU-200 is the only meter in the market which uses all measurement methods.
It allows to take the measurements of:
Additionally:
*Bluetooth communication from serial number E30001
Electric security:
Rated operational conditions:
Other technical data:
Measurement of interference voltage
| Range | Resolution | Accuracy | 
| 0…100 V | 1 V | ±(2% m.v. + 3 digits) | 
Measurement of interference frequency
| Range | Resolution | Accuracy | 
| 15…450 Hz | 1 Hz | ±(1% m.v. + 2 digits) | 
Measurement of earthing resistance (method 3- and 4-pole) 
 measurement range to IEC61557 – 5: 0,100 Ω…19,9 kΩ
| Range | Resolution | Accuracy | 
| 0,000…3,999 Ω | 0,001 Ω | ±(2% m.v. + 4 digits) | 
| 4,00…39,99 Ω | 0,01 Ω | ±(2% m.v. + 2 digits) | 
| 40,0…399,9 Ω | 0,1 Ω | |
| 400…3999 Ω | 0,001 kΩ | |
| 4,00k…19,99 kΩ | 0,01 kΩ | ±(5% m.v. + 2 digits) | 
Measurement of continuity of equipotential bondings and protective conductors (Rcont) 
 measurement range to IEC61557 – 4: 0,045 Ω…19,99 kΩ
| Range | Resolution | Accuracy | 
| 0,000…3,999 Ω | 0,001 Ω | ±(2% m.v. + 4 digits) | 
| 4,00…39,99 Ω | 0,01 Ω | ±(2% m.v. + 2 digits) | 
| 40,0…399,9 Ω | 0,1 Ω | |
| 400…3999 Ω | 0,001 kΩ | |
| 4,00k…19,99 kΩ | 0,01 kΩ | ±(5% m.v. + 2 digits) | 
Measurement of resistance of auxiliary electrodes RH and RS
| Range | Range | Accuracy | 
| 0…999 Ω | 1 Ω | ±(5% (RS+RE+RH) + 8 digits) | 
| 1,00k…9,99 kΩ | 0,01 kΩ | |
| 10,0k…19,9 kΩ | 0,1 kΩ | 
Measurement of multiple earthing resistance with using the clamp and auxiliary
 electrodes (3p + clamp)
| Range | Resolution | Accuracy | 
| 0,000…3,999 Ω* | 0,01 Ω | ±(8% m.v. + 4 digits) | 
| 10,0…99,9 Ω | 0,01 Ω | ±(8% m.v. + 3 digits) | 
| 100…999 Ω | 0,1 Ω | |
| 1,00k…1,99 kΩ | 1 Ω | 
* – in range 0,000…0,045 Ω the accuracy is not specified.
Measurement of multiple earthing resistance with using double clamps
| Range | Resolution | Accuracy | 
| 0,00…19,99 Ω | 0,1 Ω | ±(10% m.v. + 3 digits) | 
| 20,0…149,9 Ω | 0,1 Ω | ±(20% m.v. + 3 digits) | 
Measurement of ground resistivity Measurement method: Wennera, ρ=2πLRE
| Range | Resolution | Accuracy | 
| 0,0…199,9 Ωm | 0,1 Ωm | depending on measurement accuracy RE with 4p method, but not less than ±1 digit | 
| 200…1999 Ωm | 1 Ωm | |
| 2,00k…19,99 kΩm | 0,01 kΩm | |
| 20,0k…99,9 kΩm | 0,1 kΩm | |
| 100k…999 kΩm | 1 kΩm | 
L – distance between probes: 1…50 m
  
Measurement of AC current (leakage)
| Range | Resolution | Accuracy | 
| 0,1…99,9 mA 1 | 0,1 mA | ±(8% m.v. + 5 digits) | 
| 100…999 mA 1 | 1 mA | ±(8% m.v. + 3 digits) | 
| 1,00…4,99 A 1,2 | 0,01 A | ±(5% m.v. + 5 digits)1 unspecified 2 | 
| 5,00…9,99 A 1,2 | 0,01 A | ±(5% m.v. + 5 digits) | 
| 10,0…99,9 A 1,2 | 0,1 A | |
| 100…300 A 1,2 | 1 A | 
1 – receiving clamp (diameter 52 mm) – C-3
 2 – flexible clamp (Rogowsky coil) with diameter 400 mm – F-1
Measurement of dynamic earthing resistance (RD) with impulse wave method (4p )
| Range | Resolution | Accuracy | 
| 0,0…99,9 Ω | 0,1 Ω | ±(2,5% m.v. + 3 digits) | 
| 100…199 Ω | 1 Ω | 
choice impulse edges: 4/10μs, 8/20μs, 10/350μs
„m.v.”- measured value