4 analog outputs, 0 to 10 V, 12 bits
Analog Outputs | 4 channels |
Resolution in Ranges | 12 bits, 2.44 mV/bit |
Output Current Range | 0 to 10 VDC (single-ended) |
Data Format | 16-bit integer (2’s complement) |
Accuracy | • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C |
Output Impedance | Max. 5K ohms |
Conversion Time | 2 ms for all channels |
Power Consumption | 60 mA @ 5 VDC |
Isolation | I/O to logic (photocoupler isolation) |
Wiring | I/O cable max. AWG14 |
Model No. | Description | |
---|---|---|
M-4410 | 4 analog outputs, 0 to 10 V, 12 bits |