ioPAC 8600 Series Expansion Modules

I/O Modules for ioPAC 8600 series modular programmable controllers

L20151123150510

Features and Benefits

  • 86M-1620D-T: 16 digital inputs, 24 to 110 VDC, channel LED, sink type
  • 86M-1832D-T: 8 channel-to-channel isolated DIs, 24 VDC, channel LED, sink/source type
  • 86M-2604D-T: 6 relays, channel LED, form A (N.O.) type
  • 86M-2830D-T: 8 channel-to-channel isolated DOs, 24 VDC, channel LED, sink-type
  • 86M-4420-T: 4 analog outputs, 0 to 10 V or -10 to 10 V or 0 to 20 mA or 4 to 20 mA
  • 86M-5212U-T: 2-port 2-wire Ethernet switch
  • 86M-5250-T: 2 CAN ports, channel LED

Introduction

Moxa’s 86M series modules with ch-to-ch isolated DIs, ch-to-ch isolated DOs, relays, and AOs provide more I/O options for the ioPAC 8600 series. Combined with 85M modules, enough options are now available to allow users to select the best I/O combination for their target application. All 86M modules are designed for railway industry applications, and as such are compliant with EN 50121-3-2, EN 50121-4, and EN 50155. In addition, the modules support a wide operating temperature range of -40 to 75°C.

CPU10 Series Specifications
• Computer
CPU Type32-bit ARM9 192 MHz CPU
OSLinux
ClockReal-time clock with super capacitor (retains charge for 7 days)
• Memory
SDRAM64 MB
Flash32 MB (10 MB reserved for user)
FRAM128 KB
microSD™ SlotUp to 32 GB (SD 2.0 compatible)
Note: For units operating in extreme temperatures, industrial-grade, wide-temperature microSD cards are required.
• Switches & Buttons
Rotary Switch0 to 9
ButtonReset to factory defaults
• Ethernet Interface
LAN2 x 10/100 Mbps, Ethernet bypass or 2 MACs (IPs), jumper selectable, RJ45 or M12
Protection1.5 kV magnetic isolation
Automation LanguagesC/C++ or IEC 61131-3
ProtocolsModbus TCP/RTU (master/slave), SNMP, TCP/IP, UDP, DHCP, BOOTP, SNTP, SMTP
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current200 mA @ 24 VDC
• MTBF (mean time between failures)
Time1,032,466 hrs
StandardTelcordia SR332
PW10-15W-T Specifications
• Power
Input Voltage24 to 110 VDC (16.8 to 154 VDC)
Note: Compliant with EN 50155 at 24/48/60/72/110 VDC
Wattage15 W
Galvanic Isolation3k VDC
Dual-Power InputYes
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• MTBF (mean time between failures)
Time1,579,517 hrs
StandardTelcordia SR332
86M-1832D-T Specifications
• Inputs and Outputs
Digital Inputs8 channels
IsolationTo system: 3k VDC or 2k Vrms
Channel-to-channel: 1k VDC
• Digital Input
Sensor TypeWet contact (NPN or PNP)
I/O ModeDI, counter, or frequency
Wet Contact (DI+ to DI-)• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Counter Frequency5 kHz
Digital Filtering Time IntervalSoftware selectable (by 0.1 ms)
• Physical Characteristics
WiringI/O cable, 16 AWG (max.)
ConnectorSpring-type terminal block
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current12.6 mA @ 24 VDC
• MTBF (mean time between failures)
Time1,149,108 hrs
StandardTelcordia SR332
86M-2830D-T Specifications
• Inputs and Outputs
Digital Outputs8 channels
IsolationTo system: 3k VDC or 2k Vrms
Channel-to-channel: 1k VDC
• Digital Output
TypeSink
I/O ModeDO or PWM
Pulse Output Frequency1 kHz
Short Circuit Protection750 mA @ 25°C
Over-Voltage Protection41 VDC
Over-Current Protection2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown175°C (typical), 150°C (min.)
Current Rating200 mA per channel
• Physical Characteristics
WiringI/O cable, 16 AWG (max.)
ConnectorSpring-type terminal block
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current76.7 mA @ 24 VDC
• MTBF (mean time between failures)
Time1,766,037 hrs
StandardTelcordia SR332
86M-2604D-T Specifications
• Inputs and Outputs
Relays6 channels
IsolationTo System: 3k VDC or 2k Vrms
• Relay
TypeForm A (N.O.)
I/O modeDO or PWM
Pulse Output Frequency0.33 Hz
Contact Current RatingResistive Load: 5 A @ 30 VDC, 250 VAC
Relay On/Off Time10 ms (max.)
Initial Insulation Resistance1000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance5,000,000 operations
Electrical Endurance60,000 operations @ 5 A resistive load
Contact Resistance100 milli-ohms (max.)
• Physical Characteristics
WiringI/O cable, 16 AWG (max.)
ConnectorSpring-type terminal block
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current127 mA @ 24 VDC
• MTBF (mean time between failures)
Time4,173,843 hrs
StandardTelcordia SR332
86M-4420-T Specifications
• Inputs and Outputs
Analog Outputs4 channels
IsolationTo system: 3k VDC or 2k Vrms
• Analog Output
Resolution12 bits
Output range0 to 10 V, -10 to 10 V, 0 to 20 mA, 4 to 20 mA
I/O modeStatic or Waveform mode
Voltage Output10 mA (max.)
Accuracy±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Current Load ResistanceInternal Power: 400 ohms
External 24 VDC Power: 1000 ohms
Update RateSoftware polling or waveform mode
Waveform TypeSine, Triangle, Square
Wavemode Frequency125 Hz
• Physical Characteristics
WiringI/O cable, 16 AWG (max.)
ConnectorSpring-type terminal block
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current94.2 mA @ 24 VDC (voltage)
143.8 mA @ 24 VDC (current)
• MTBF (mean time between failures)
Time2,409,345 hrs
StandardTelcordia SR332
86M-1620D-T Specifications
• Inputs and Outputs
Digital Inputs16 channels
IsolationTo system:
3k VDC or 2k Vrms
• Digital Input
TypePNP
I/O modeDI
Logic Definition• On: channel voltage > 0.3 x (external power voltage)
• Off: channel voltage < 0.15 x (external power voltage)
Scan Period8 ms (typ.)
Scan on Time0.5 ms
Debouncing FunctionSoftware disable/enable
Debouncing Time1 to 15 ms (software-selectable)
Common Type8 points per COM
• Physical Characteristics
WiringI/O cable, 16 AWG (max.)
ConnectorSpring-type terminal block
Channel LEDYes
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current12.6 mA @ 24 VDC
• MTBF (mean time between failures)
Time1,115,244 hrs
StandardTelcordia SR332
86M-5212U-T Specifications
• Ethernet Communication
InterfaceTwo 2-wire Ethernet ports
IsolationTo system: 3k VDC or 2k Vrms
• Standards
Supported Standards100BASE-TX IEEE 802.3u
10BASE-T IEEE 802.3
100 Mbps BroadR-Reach®
10 Mbps BroadR-Reach®
• Physical Characteristics
WiringCAT 5 standard cable with M12 D-code male connection
ConnectorM12 (D-code, female) x 2
Channel LEDYes
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current578 mA @ 3.3 VDC
• MTBF (mean time between failures)
Time2,498,942 hrs
StandardTelcordia SR332
86M-5250-T Specifications
• Serial Communication
Interface2 CAN ports
IsolationTo system: 3k VDC or 2k Vrms
• CAN Bus Communication
ProtocolsCAN 2.0A
CAN 2.0B
CANopen DS301, V4.02
CANopen DS401
Speed10/20/50/125/250/500/800 kbps, 1 Mbps
Termination ResistorN/A, 120 ohms (by DIP)
• Physical Characteristics
ConnectorDB9 male
Channel LEDYes
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
• Power Requirements
Input Current60 mA @ 24 VDC
• MTBF (mean time between failures)
Time3,306,609 hrs
StandardTelcordia SR332
Common Specifications
• Power Requirements
Input Voltage24 to 110 VDC (16.8 to 154 VDC)
• Environmental Limits
Operating Temperature-40 to 75°C (-40 to 176°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity5 to 95% (non-condensing)
ShockIEC 60068-2-27
VibrationIEC 60068-2-6
• Standards and Certifications
SafetyUL 508
EMCEN 55032/24
EMIFCC Part 15 Subpart B Class A, CISPR 32
EMSIEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS:
80 MHz to 1000 MHz: 3 V/m
1400 MHz to 2100 MHz: 3 V/m
2100 MHz to 2700 MHz: 1 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L);
Rail TrafficEN 50155 (essential compliance*), EN 50121-3-2, EN 50121-4
*Moxa defines “essential compliance” to include those EN 50155 requirements that make products more suitable for rolling stock railway applications.
• Warranty
Warranty Period5 years
DetailsSee www.moxa.com/warranty

Available Models

Model No.Description
86M-1620D-T16 DIs, sink, 24 to 110 VDC, channel LED, -40 to 75°C operating temperature
86M-1832D-T8 DIs, sink/source, 24 VDC, ch-to-ch isolation, channel LED, -40 to 75°C operating temperature
86M-2604D-T6 relays, form A (N.O.), channel LED, -40 to 75°C operating temperature
86M-2830D-T8 DOs, sink, 24 VDC, ch-to-ch isolation, channel LED, -40 to 75°C operating temperature
86M-4420-T4 AOs, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20 mA, -40 to 75°C operating temperature
86M-5212U-T2-port 2-wire Ethernet switch, -40 to 75°C operating temperature
86M-5250-T2 CAN ports, -40 to 75°C operating temperature

backtotop
iopac-8600-series-expansion-modules-safenergy-i-din-moxa-ti-vit-nam