The TCF-142 media converters are equipped with a multiple interface circuit that can handle RS-232 or RS-422/485 serial interfaces and multi-mode or single-mode fiber. TCF-142 converters are used to extend serial transmission up to 5 km (TCF-142-M with multi-mode fiber) or up to 40 km (TCF-142-S with single-mode fiber). The TCF-142 converters can be configured to convert either RS-232 signals, or RS-422/485 signals, but not both at the same time.
The TCF-142 converters can automatically detect the serial baudrate. This is an extremely convenient feature. Even if a device’s baudrate is changed, the signal will still be transmitted through the media converter without any data loss.
The TCF-142 converters can be used to connect serial devices to a fiber ring. To form the ring, connect the Tx port of one TCF-142 to the Rx port of a neighboring converter. Once the ring is set up, simply use the DIP switches to configure the TCF-142 converters for “ring mode.” When one node transmits a signal, the signal travels around the ring until it returns back to the transmitting unit, which then blocks the signal. With the TCF-142, you can set up fiber rings that have a total circumference of up to 100 km.
ADDC® is a patented hardware data flow solution developed by Moxa to handle RS-485 data direction control. ADDC® senses and controls RS-485 data direction automatically, making it unnecessary to use the hand shaking signal.
• Optical-Fiber Side | |
Fiber Connector | SC or ST |
Fiber Cable Requirements | |
Ring Transmission | Half-duplex |
Point-to-Point Transmission | Half-duplex or full-duplex |
• RS-232/422/485 Side | |
Connector | Terminal Block |
RS-232 Signals | Tx, Rx, GND |
RS-422 Signals | TxD+, TxD-, RxD+, RxD-, GND |
RS-485-4w Signals | TxD+, TxD-, RxD+, RxD-, GND |
RS-485-2w Signals | Data+, Data-, GND |
Baudrate | 50 bps to 921.6 kbps |
• Physical Characteristics | |
Housing | Metal |
Dimensions | Without ears: 67 x 100 x 22 mm (2.64 x 3.94 x 0.87 in) With ears: 90 x 100 x 22 mm (3.54 x 3.94 x 0.87 in) |
Weight | 320 g (0.71 lb) |
• Environmental Limits | |
Operating Temperature | Standard Models: 0 to 60°C (32 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F) |
Storage Temperature | -40 to 75°C (-40 to 167°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
• Power Requirements | |
Input Voltage | 12 to 48 VDC |
Input Current | 140 mA @ 12 VDC |
Power Line Protection | 1 kV Burst (EFT), EN61000-4-4 1 kV Surge, EN61000-4-5 |
Voltage Reversal Protection | Protects against V+/V- reversal |
Overcurrent Protection | 1.1 A (protects against two signals shorted together) |
• Standards and Certifications | |
Safety | UL 60950-1 |
EMC | EN 55032/24 |
EMI | CISPR 32, FCC Part 15B Class B |
EMS | EN 61000-4-2 (ESD): Contact: 6 kV; Air: 8 kV EN 61000-4-3 (RS): 80 MHz to 1 GHz: 10 V/m EN 61000-4-4 (EFT): Power: 1 kV EN 61000-4-5 (Surge): Power: 1 kV EN 61000-4-6 (CS): 150 kHz to 80 MHz: 3 V/m EN 61000-4-8 (PFMF) |
Green Product | RoHS, CRoHS, WEEE |
• MTBF (mean time between failures) | |
Time | 780,480 hrs |
Standard | Telcordia (Bellcore), GB |
• Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |
Model No. | Description | |
---|---|---|
TCF-142-M-SC | RS-232/422/485 to multi-mode optical fiber media converter with fiber ring support and SC connector, 0 to 60°C operating temperature | |
TCF-142-M-ST | RS-232/422/485 to multi-mode optical fiber media converter with fiber ring support and ST connector, 0 to 60°C operating temperature | |
TCF-142-S-SC | RS-232/422/485 to single-mode optical fiber media converter with fiber ring support and SC connector, 0 to 60°C operating temperature | |
TCF-142-S-ST | RS-232/422/485 to single-mode optical fiber media converter with fiber ring support and ST connector, 0 to 60°C operating temperature | |
TCF-142-M-SC-T | RS-232/422/485 to multi-mode optical fiber media converter with fiber ring support and SC connector, -40 to 75°C operating temperature | |
TCF-142-M-ST-T | RS-232/422/485 to multi-mode optical fiber media converter with fiber ring support and ST connector, -40 to 75°C operating temperature | |
TCF-142-S-SC-T | RS-232/422/485 to single-mode optical fiber media converter with fiber ring support and SC connector, -40 to 75°C operating temperature | |
TCF-142-S-ST-T | RS-232/422/485 to single-mode optical fiber media converter with fiber ring support and ST connector, -40 to 75°C operating temperature |
Model No. | Description | |
---|---|---|
DK35A | DIN-Rail Mounting Kit (35 mm) |
tcf-142-series-safenergy-i-din-moxa-ti-vit-nam