The Isolated Timing Repeater (previously known as the MOFR) is a compact DIN rail mountable signal repeater that performs a number of tasks, including converting time sync signals , boosting signal strengths and converting one type of signal to another. The Isolated Timing Repeater is completely electrically isolated and it will provide your IEDs (Intelligent Electronic Devices) with an additional layer of electrical protection.
Low Voltage Copper | Low Voltage Fiber | High Voltage MOSFET | |
Physical | |||
Design: UL94-V0 polycarbonate flame retardant din rail mount case with IP40 (Ingress Protection rating). | √ | √ | √ |
Dimensions: (W) 55 mm x (D) 60 mm x (H) 90 mm | √ | √ | √ |
Weight: | 0.15 Kg | 0.15 Kg | 0.15 Kg |
Copper: 5 V, 2 mA max TTL compatible (2 Pin screw terminal) | √ | √ | √ |
Fiber: ST Fiber (62.5/125 um) multi-mode Sensitivity -34.4 dBm | √ | √ | |
Outputs | |||
Copper TTL: 0 – 5 V, 150 mA, fused (2 Pin screw terminal) | √ | √ | |
Copper RS232: ±10 V, 15 mA (max) (2 Pin screw terminal) | √ | √ | |
Copper RS422/RS485: ±5 V, 50 RS422 unit loads (RS485 compatible) (2 Pin screw terminal) | √ | √ | |
Fiber: ST Fiber (62.5/125 um) multi-mode | √ | √ | |
HV MOSFET: 300 Vdc, 1A (2 Pin screw terminal) | √ | ||
Optional Output | |||
AM IRIG-B 8 V 120Ω output impedance | √ | √ | |
Environmental | |||
Power supply options: – Low(12-36Vdc) – Med(20-72Vdc) – High(90-300Vdc) | √ | √ | √ |
Power Drain: | 1.5 W max | 1.5 W max | 1.5 W max |
Operating temperature: | -10 to +65°C | -10 to +65°C | -10 to +65°C |
Humidity: | 10% to 95% non-condensing | 10% to 95% non-condensing | 10% to 95% non-condensing |
Signal Delays | |||
Input to copper/fiber output: | 85 ±10 ns | 85 ±10 ns | 85 ±10 ns |
Input to HV MOSFET Output | 60 μs (Typical) | ||
Isolation | |||
Power to I/O: | 2 kV | 2 kV | 2 kV |
Input to Earth: | 3.5 kV (min) | 3.5 kV (min) | 3.5 kV (min) |
Output to Earth: | 3.5 kV (min) | 3.5 kV (min) | 3.5 kV (min) |
itr-safenergy-i-din-moxa-ti-vit-nam