The Isolated Timing Repeater (previously known as the MOFR) is a compact DIN rail mountable signal repeater that performs a number of tasks, including converting time sync signals , boosting signal strengths and converting one type of signal to another. The Isolated Timing Repeater is completely electrically isolated and it will provide your IEDs (Intelligent Electronic Devices) with an additional layer of electrical protection.

Key Features:

  • Extend the distance of an IRIG-B or Pulse signal
  • Provide isolation between A & B Protection Systems or between IEDs
  • Converts a TTL signal from copper to fiber / fiber to copper
  • Converts a TTL signal to a digital High Voltage MOSFET signal
  • Reduces wiring to panels of equipment

Input/Output Signals:

  • Copper to fiber
  • Fiber to copper
  • RS232 output
  • RS422 output
  • Fiber output
  • TTL output
  • HV MOSFET output
  • Optional AM IRIG-B output
   
Low Voltage CopperLow Voltage FiberHigh Voltage MOSFET
Physical
Design:
UL94-V0 polycarbonate flame retardant din rail mount case with IP40 (Ingress Protection rating).
Dimensions:
(W) 55 mm x (D) 60 mm x (H) 90 mm
Weight:0.15 Kg0.15 Kg0.15 Kg
Copper: 
5 V, 2 mA max TTL compatible
(2 Pin screw terminal)
Fiber:
ST Fiber (62.5/125 um)
multi-mode
Sensitivity -34.4 dBm
Outputs
Copper TTL:
0 – 5 V, 150 mA, fused
(2 Pin screw terminal)
Copper RS232:
±10 V, 15 mA (max)
(2 Pin screw terminal)
Copper RS422/RS485:
±5 V, 50 RS422 unit loads (RS485 compatible)
(2 Pin screw terminal)
Fiber:
ST Fiber (62.5/125 um)
multi-mode
HV MOSFET:
300 Vdc, 1A
(2 Pin screw terminal)
Optional Output
AM IRIG-B
8 V
120Ω output impedance
Environmental
Power supply options:
– Low(12-36Vdc)
– Med(20-72Vdc)
– High(90-300Vdc)
Power Drain:1.5 W max1.5 W max1.5 W max
Operating temperature:-10 to +65°C-10 to +65°C-10 to +65°C
Humidity:10% to 95% non-condensing10% to 95% non-condensing10% to 95% non-condensing
Signal Delays
Input to copper/fiber output:85 ±10 ns85 ±10 ns85 ±10 ns
Input to HV MOSFET Output60 μs (Typical)
Isolation
Power to I/O:2 kV2 kV2 kV
Input to Earth:3.5 kV (min)3.5 kV (min)3.5 kV (min)
Output to Earth:3.5 kV (min)3.5 kV (min)3.5 kV (min)

backtotop