The MZC310S is a professional portable meter for testing electrical installations with over-current circuit breakers. The instrument measures short-circuit L-PE, L-N and L-L loop and prospective short-circuit loop current. A measurements can be done either with low testing current (up to 42 A) with 2-pole method or high testing current (up to 280 A) with 4-pole method that enables measurements with very high accuracy and resolution. The results can be stored in the internal memory and send to a computer via serial interface.
Measurement of very low short circuit loop impedances (with resolution 0,1 mΩ) with a current of 150 A at 230 V; maximum 280 A at 440 V or measurement with a current of 23 A at 230 V; maximum 42 A at 440 V.
Touch voltage and touch shock voltage measurement (with resistor 1 kΩ).
AC voltage measurement in range 0…440 V.
Memory for 999 measurement results with an ability to transfer the data to a PC.
Meter meets the requirements of the standard EN 61557.
Electric security:
Other technical data:
Rated operational conditions:
Voltages measurement (True RMS)
| Range | Resolution | Accuracy | 
| 0…440 V | 1 V | ±(2% m.v. + 2 digits) | 
Frequency measurement (for voltages within the range 50…440 V)
| Range | Resolution | Accuracy | 
| 45,0…65,0 Hz | 0,1 Hz | ±(0,1% m.v. + 1 digits) | 
Short circuit loop parameters measurement using high current (4p, Imax=280 A)
High-current of measurement of short circuit loop impedance ZS:
 measuring range according to IEC61557: 7,2 mΩ…1999 mΩ
| Range | Resolution | Accuracy | 
| 0…199,9 mΩ | 0,1 mΩ | ±(2% m.v. + 2 mΩ) | 
| 200…1999 mΩ | 1 mΩ | 
Short circuit resistance RS and reactance XS display range
| Range | Resolution | Accuracy | 
| 0…199,9 mΩ | 0,1 mΩ | ±(2% m.v. + 2 mΩ) impedance reading for a particular measurement | 
| 200…1999 mΩ | 1 mΩ | 
Prospective short circuit loop current
 measuring range according to IEC 61557:
| Range | Resolution | Accuracy | 
| 115,0…199,9 A | 0,1 A | accuracy of the current indication computed, respectively, with the use of resistance measurement | 
| 200…1999 A | 1 A | |
| 2,00…19,99 kA | 0,01 kA | |
| 20,0…199,9 kA | 0,1 kA | |
| 200 kA…* | 1 kA | 
Measurement of short circuit loop using standard current (2p, Imax=42 A)
Touch voltage measurement UST (shock voltage UT)
| Range | Resolution | Accuracy | 
| 0…100 V | 1 V | ±(10% m.v. + 2 digits) | 
Short circuit loop impedance ZS measurement:
 measuring range according to IEC61557: 0,13 Ω…199,9 Ω for 1,2 m long test leads
| Range | Resolution | Accuracy | 
| 0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) | 
| 20,0…199,9 Ω | 0,1 Ω | ±(3% m.v. + 3 digits) | 
Short circuit resistance RS and reactance XS display range
| Range | Resolution | Accuracy | 
| 0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) impedance reading for a particular measurement | 
| 20,0…199,9 Ω | 0,1 Ω | ±(2% m.v. + 3 digits) impedance reading for a particular measurement | 
Prospective short circuit loop current
| Range | Resolution | Accuracy | 
| 1,150…1,999 A | 0,001 A | accuracy of the current indication computed, respectively, with the use of resistance measurement | 
| 2,00…19,99 A | 0,01 A | |
| 20,0…199,9 A | 0,1 A | |
| 200…1999 A | 1 A | |
| 2,00…19,99 kA | 0,01 kA | |
| 20,0…40,0 kA | 0,1 kA | 
„m.v.” – measured value

mzc-310s-safenergy-i-din-moxa-ti-vit-nam