The meter has been designed for fitters and measurement technicians performing services in residential buildings, office blocks, manufacturing plants and any facilities possessing a low-voltage electrical system. The instrument is also recommended for electrical maintenance personnel.
Measurements of impedance in a short-circuit loop Z within the range S
of 0.24…200 Ω
Short-circuit current IK: 1,15 – 958,3 A (Un =230 V)
AC voltage measurement: 0 – 440 V
Display range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(2,5% m.v + 5 digits) |
20,0…199,9 Ω | 0,1 Ω | ±(2,5% m.v + 3 digits) |
100…200 Ω | 1 Ω | ±(3% m.v + 3 digits) |
Short-circuit resistance RS and reactance XS display range:
Display range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(5% m.v. + 5 digits) of ZS value |
Calculated and displayed fori ZS <10 Ω.
Short-circuit current IK display
Measuring range according to IEC 61557 can be calculated based on ZS
measuring range and rated voltage values.
Display range | Resolution | Accuracy |
1,15…9,99 A | 0,01 A | Calculated based on the accuracy for the short-circuit loop accuracy |
10,0…99,9 A | 0,1 A | |
100…999 A | 1 A | |
1,00…9,99 kA | 0,01 kA | |
10,0…40,0 kA | 0,1 kA |
Short-circuit loop impedance ZS measurement
Measuring cable | ZS measuring range |
1,2m | 0,24…200 Ω |
5m | 0,26…200 Ω |
10m | 0,28…200 Ω |
20m | 0,35…200 Ω |
Voltage measurement
Display range | Resolution | Accuracy |
0…440 V | 1 V | ±(2,5% m.v + 3 digits) |
Electrical safety:
Other technical data:
mzc-20e-safenergy-i-din-moxa-ti-vit-nam