Possible measurements:

  • earth resistance measurment with 3-pole method,
  • measurement of continuity of equipotential bondings and protective conductors with auto-zero function – with current 200 mA,
  • resistance measurement using 2-pole method.

Additionally:

  • AUTO-OFF function after 5 minutes,
  • indication of battery state.

It allows to take:

  • earth resistance measurement using auxiliary probes with 3-pole method,
  • resistance measurement using 2-pole method,
  • measurement of continuity of equipotential bondings and protective conductors (meeting the requirements of IEC 61557 – 4) with auto-zero function – with current 200 mA.

Additionally:

  • AUTO-OFF function after 5 minutes,
  • indication of battery state.

Measurement of earthing resistance
measurement range to IEC61557 – 5:

  • 0,50 Ω…1,99 kΩ Un=50 V;
  • 0,68 Ω…1,99 kΩ dla Un=25 V
RangeResolutionAccuracy
0,00…9,99 Ω0,01 Ω±(2% m.v. + 3 digits)
10,0…99,9 Ω0,1 Ω
100…999 Ω1 Ω
1,00…1,99 kΩ0,01 kΩ
  • measurement current: under short circuit >20 mA,
  • voltage on open terminals: selectable 25 V AC or 50 V AC,
  • frequency of measurement current: 125 Hz

Measurement of resistance of auxiliary electrodes RH i RS

RangeResolutionAccuracy
0…999 Ω1 Ω±(5% (RS+RE+RH) + 3 digits)
1,00k…9,99 kΩ0,01 kΩ
10,0k…50,0 kΩ0,1 kΩ

Measurement of interference voltage UN (RMS)

RangeResolutionAccuracy
0…100 V1 V±(2% m.v. + 3 digits)

Measuremet of continuity of equipotential bondings and protective conductors
measurement range to IEC61557 – 4: 0,13…199 Ω

RangeResolutionAccuracy
0,00…9,99 Ω0,01 Ω±(2% m.v. + 3 digits)
10,0…99,9 Ω0,1 Ω
100…199 Ω1 Ω
  • measuring method: technical 2-pole method,
  • max. voltage on open terminals: 13 V,
  • measurement current: under short circuit >200 mA,
  • auto-zero function for measurement leads0,13 Ω…199 Ω

Electric security:

  • type of insulation: double, according to IEC 61010 – 1and IEC 61557
  • measurement category: CAT IV 300 V acc. to IEC 61010 – 1
  • protection class acc. to EN 60529: IP54

Rated operational conditions:

  • operation temperature: -10…+55°C
  • storage temperature: -20…+70°C
  • humidity: 20…80%

Other technical data:

  • power supply: alkaline batteries or NiMH rechargeable batteries, size AA (8 pcs)
  • LCD display: segment, backlit
  • weight with batteries: approx. 1,3 kg
  • dimensions: 260 x 190 x 60 mm
  • electromagnetic compatibility: according to IEC 61000 – 6 – 3 and IEC 61000 – 6 – 2