It allows to take:
- earth resistance measurement using auxiliary probes with 3-pole method,
- resistance measurement using 2-pole method,
- measurement of continuity of equipotential bondings and protective conductors (meeting the requirements of IEC 61557 – 4) with auto-zero function – with current 200 mA.
Additionally:
- AUTO-OFF function after 5 minutes,
- indication of battery state.
Measurement of earthing resistance
measurement range to IEC61557 – 5:
- 0,50 Ω…1,99 kΩ Un=50 V;
- 0,68 Ω…1,99 kΩ dla Un=25 V
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω |
100…999 Ω | 1 Ω |
1,00…1,99 kΩ | 0,01 kΩ |
- measurement current: under short circuit >20 mA,
- voltage on open terminals: selectable 25 V AC or 50 V AC,
- frequency of measurement current: 125 Hz
Measurement of resistance of auxiliary electrodes RH i RS
0…999 Ω | 1 Ω | ±(5% (RS+RE+RH) + 3 digits) |
1,00k…9,99 kΩ | 0,01 kΩ |
10,0k…50,0 kΩ | 0,1 kΩ |
Measurement of interference voltage UN (RMS)
0…100 V | 1 V | ±(2% m.v. + 3 digits) |
Measuremet of continuity of equipotential bondings and protective conductors
measurement range to IEC61557 – 4: 0,13…199 Ω
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω |
100…199 Ω | 1 Ω |
- measuring method: technical 2-pole method,
- max. voltage on open terminals: 13 V,
- measurement current: under short circuit >200 mA,
- auto-zero function for measurement leads0,13 Ω…199 Ω
Electric security:
- type of insulation: double, according to IEC 61010 – 1and IEC 61557
- measurement category: CAT IV 300 V acc. to IEC 61010 – 1
- protection class acc. to EN 60529: IP54
Rated operational conditions:
- operation temperature: -10…+55°C
- storage temperature: -20…+70°C
- humidity: 20…80%
Other technical data:
- power supply: alkaline batteries or NiMH rechargeable batteries, size AA (8 pcs)
- LCD display: segment, backlit
- weight with batteries: approx. 1,3 kg
- dimensions: 260 x 190 x 60 mm
- electromagnetic compatibility: according to IEC 61000 – 6 – 3 and IEC 61000 – 6 – 2