Possible measurements:
Short-circuit loop measurement:
Short-circuit loop measurement with resolution 0,01 Ω, in distribution network without tiggering RCD (IΔn≥30 mA):
Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000 mA. (Type AC, A and B).
Measurement of insulation resistance:
Measurement of earthing resistance.
Bi-directional testing of PE wire continuity using 200 mA current.
Phase sequence testing.
Memory is divided into 10 memory banks each of them containing 99 memory cells.
Battery charge indicator.
AUTO-OFF function.
USB interface.
Short-circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
Measurement using 23/40 A current measurement range in accordance with IEC 61557: 0,13…1999,9 Ω
(for 1,2 m lead ):
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(5% m.v. + 3 dgt) |
20,0…199,9 Ω | 0,1 Ω | |
200…1999 Ω | 1 Ω |
rated voltage: 95…270 V (for ZL-PE i ZL-N) and 95…440 V (for ZL-L)
frequency: 45…65 Hz
Short-circuit loop impedance measurement ZL-PERCD
Measurement using 15 mA current measurement range in accordance with
IEC 61557: 0,50…1999,9 Ω
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(6% m.v. + 10 dgt) |
20,0…199,9 Ω | 0,1 Ω | ±(6% m.v. + 5 dgt) |
200…1999 Ω | 1 Ω |
rated voltage: 95…270 V
frequency: 45…65 Hz
Measurement of earthing RE
Rated voltage in accordance with IEC 61557 – 5:
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 4 dgt) |
10,0…99,9 Ω | 0,1 Ω | ±(2% m.v. + 3 dgt) |
100…999 Ω | 1 Ω | |
1,00…1,99 kΩ | 0,01 kΩ |
Insulation resistance measurement
Measurement range in accordance with IEC 61557 – 2:
Display range*) | Resolution | Accuracy**) |
0…1999 kΩ | 1 kΩ | ±(3% m.v. + 8 dgt) |
2,00…19,99 MΩ | 0,01 MΩ | |
20,0…199,9 MΩ | 0,1 MΩ | |
200…999 MΩ | 1 MΩ | |
1,00…3,00 GΩ | 0,01 GΩ | ±(4% m.v. + 6 dgt) |
*) limited to measurement range.
**) with UNI-Schuko additional error ±2%.
Phase sequence
Measurement of the active P, passive Q and apparent S power and cosφ
– measurement cosφ: 0,00…1,00 (resolution 0,01)
Low voltage test of the circuit and insulation continuity
Test of PE wire continuity using a ±200 mA current
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 dgt) |
20,0…199,9 Ω | 0,1 Ω | |
200…400 Ω | 1 |
Voltage on open terminals: 4…9 V
Test current at R<2 Ω: min. 200 mA at rated battery voltage
Autocalibration of test leads
Measurements for both polarizations of the current
RCD trigger and response time test tA (for tA mode)Measurement ranges
in accordance with IEC 61557: 0 ms … up to the upper bound of the displayed value
Breaker Type | Test Current Multiplier | Measurement Range | Resolution | Accuracy |
Standard | 0,5*IΔn | 0…300 ms | 1 ms | ± (2% m.v. + 2 dgt) |
1*IΔn | ||||
2*IΔn | 0…150 ms | |||
5*IΔn | 0…40 ms | |||
Selective | 0,5*IΔn | 0…500 ms | ||
1*IΔn | ||||
2*IΔn | 0…200 ms | |||
5*IΔn | 0…150 ms |
Precision of the differential current: for 0,5*IΔn:-8…0% dla 1*IΔn, 2*IΔn, 5*IΔn: 0…8%
Measurement of the RCD triggering current (IA) for sine waveform testing current
Selected Current | Range | Resolution | Test Current | Accuracy |
10 mA | 3,3…10,0 mA | 0,1 mA | 0,3xIΔ..1,0xIΔ | ± 5%IΔn |
30 mA | 9,0…30,0 mA | |||
100 mA | 33…100 mA | 1 mA | ||
300 mA | 90…300 mA | |||
500 mA | 150…500 mA | |||
1000 mA | 330…1000 mA | 1 mA |
It is possible to start the measurement from the positive or negative half of the forced leaking current
Measurement of the RDC triggering current (IA ) for a unidirectional half period sine
waveform test current with a 6 mA direct current offset
Selected Current | Range | Resolution | Test Current | Accuracy |
10 mA | 4…20,0 mA | 0,1 mA | 0,4xIΔn..2,0xIΔn | ±10%IΔn |
30 mA | 12,0…42,0 mA | 0,4xIΔn..1,4xIΔn | ||
100 mA | 40,0…140 mA | 1 mA | ||
300 mA | 120…420 mA | |||
500 mA | 200…700 mA |
Measurement of the RCD triggering current (IA ) for direct testing current
Selected Current | Range | Resolution | Test Current | Accuracy |
10 mA | 4,0…20,0 mA | 0,1 mA | 0,4xIΔn..2,0xIΔn | ±10%IΔn |
30 mA | 12,0…60,0 mA | 1 mA | ||
100 mA | 40…200 mA | |||
300 mA | 120…600 mA | |||
500 mA | 200…1000 mA |
„m.v.” measured value.
mpi-520s-safenergy-i-din-moxa-ti-vit-nam