• Insulation resistance measurement:
    • selectable measurement voltage in the 100…2500 V range with 100 V step,
    • continuous indication of insulation resistance or leakage current,
    • automatic discharge of capacitance of tested object after the insulation resistance measurement,
    • acoustic signalling of five-second periods to facilitate obtaining time characteristics,
    • measured test times T1, T2 i T3 to measure one or two absorption coefficients in 15, 60 and 600 s,
    • indication of actual test voltage during the measurement,
    • protection against measuring live objects,
    • two and three-lead measurement method,
  • Continuity measurement of protective and equipotential conductors according to EN 61557-4
  • with the >200 mA current.
  • Leakage current measurement.
  • Measurement of alternating and direct voltages in the 0…750 V range.
  • Built-in rechargeable battery pack.
  • The instruments meet the requirements of the EN 61557 standard.
  • The ability to charge from car lighter (12 V) socket (additional accessories).

Insulation resistance measurement (two-lead)
Measurement range acc. to IEC 61557-2 for RISOmin=UISOnom/IISOmax…1 TΩ (IISOmax=1 mA)

 

RangeResolutionAccuracy
0,0…999,9 kΩ0,1 kΩ±(3% m.v. + 20 digits)
1,000…9,999 MΩ0,001 MΩ
10,00…99,99 MΩ0,01 MΩ
100,0…999,9 MΩ0,1 MΩ
1,000…9,999 GΩ0,001 GΩ
10,00…99,99 GΩ0,01 GΩ
100,0…999,9 GΩ0,1 GΩ

Values of measured resistance depending on measurement voltage

 

Voltage UISOMeasurement range
100 V50 GΩ
200…400 V100 GΩ
500…900 V250 GΩ
1000…2400 V500 GΩ
2500 V1000 GΩ

Continuity measurement of protective connections and equipotential bonding with 200 mA current.
Measurement range acc. to EN 61557-4: 0,10…999 Ω

RangeResolutionAccuracy
0,00…19,99 Ω0,01 Ω±(2% m.v. + 3 digits)
20,0…199,9 Ω0,1 Ω
200…999 Ω1 Ω±(4% m.v. + 3 digits)
  • Voltage on open terminals: 4…24 V
  • Output current at R <2 Ω: ISC >200 mA
  • Compensation of test lead resistance
  • Current flowing in both directions, mean value of resistance is displayed

DC and AC voltage measurement

RangeResolutionAccuracy
0…299,9 V0,1 V±(3% m.v. + 2 digits)
300…750 V1 V±(3% m.v. + 2 digits)
  • Frequency range: 45…65 Hz

The acronym “m.v.” stands for a “measured reference value”.

 

Electrical safety:

  • type of insulation: double, in acc. with EN 61010-1 und IEC 61557
  • measurement category: IV 600 V (III 1000 V) in acc. to EN 61010-1
  • case protection rating in acc. with EN 60529: IP65

Other technical specifications:

  • power supply of the meter SONEL L-1 NiMH 9,6 V; DC 12 V 2,5 A
  • weight of the meter: approx. 0,9 kg
  • dimensions: 200 x 180 x 77 mm
  • display: LCD segment display
  • measurement results memory: 990 cells, 11880 records,
  • transmission of measurement results: USB