Power quality analyzer PQM- 703 is a technically advanced product that allows for comprehensive measurements of the quality of electricity , analysis and recording of power network parameters, for frequencies 50/60 Hz in accordance with European standard EN 50160. PQM -703 is another representative of a well, known family of analyzers line PQM- 70x . In relation to the PQM -702 has new functions like recording of transients with max. sampling frequency 10 MHz (rapid changes in voltage) and control signals. Minimal transient capturing time is 650 ns. It is intended for a very wide range of users who need to control the quality of power with a mobile device , which fulfills the requirements of a multi-sheet standard IEC 61000 for class A analyzers. This applies to measurement accuracy, measurement methods, and synchronization of time with a standard signal. The last condition is met with a built-in GPS module with an internal antenna. If the analyzer is installed inside, it is possible to use an additional antenna with a 10m-long wire. If the antenna is situated outside, GPS signal will be attainable without any problems and used for the synchronization of an internal clock.
In practice, the analyzer may be used with all network types with rated voltage from 110 V to 760 V, directly or indirectly via transducers. It works in the following networks:
Thanks to these features PQM -703 can be used in power engineering and maintenance services fields for industrial plants , as well as by persons providing services in the power network analysis field.
Possible measurements:
The device is designed to work with networks:
Supported networks:
Specification | Range | Resolution | Accuracy | |
AC | – | 0,0…760,0 V | 0,01 % Un | ±0,1% Un |
Crest Factor | Voltage | 1,00…10,00 (≤1,65 for voltage 690 V) | 0,01 | ±5% |
Current | 1,00…10,00 (≤3,6 Inom) | 0,01 | ± 5% m.v. | |
AC current TRMS | – | depends on the clamp* | 0,01 % of nominal range | ±0,1% of nominal range (add clamps accuracy) |
Frequency | – | 40,00…70,00 Hz | 0,01Hz | ±0,01 Hz |
Active, reactive, apparent power and distortion | – | depends of configuration (transformers, clamp) | up to 4 decimal places | depends on configuration (transformers, clamp) |
Active, reactive apparent energy | – | depends of configuration (transformers, clamp) | up to 4 decimal places | the same as above |
cosφ and Power Factor (PF) | – | 0,00…1,00 | 0,01 | ±0,03 |
tgφ | – | 0,00…10,00 | 0,01 | depends on Active and Reactive power accuracy |
Harmonics | Voltage | same as for AC voltage TRMS | same as for AC voltage TRMS | ±5% Uh for Uh ≥ 1% Un ±0,05% Un for Uh < 1% Un |
Current | same as for AC current TRMS | same as for AC current TRMS | ± 5% Ih for Ih ≥ 3% In ± 0,15% In for Ih < 3% In | |
Total Harmonics Distortion | Voltage | 0,0..100,0% | 0,1% | ±5% |
Current | ±5% | |||
Harmonics active and reactive power | – | depends on configuration (transformers, clamp) | depends on current and voltage minimum value | – |
Angle | – | -180,0…+180,0o | 0,1o | ±(h x 1o) |
K-Factor | – | 1,0…50,0 | 0,1 | ±10% |
Flicker | – | 0,20…10,00 | 0,01 | ±5% |
Unbalance | Voltage and Current | 0,0…20,0% | 0,1% | ±0,15% (absolute error) |
Mains signalling | Voltage | 5…3000 Hz | 0,01 Hz | ±0,15% Uh for 1…3% Uh ,5% Un for 3…15% Uh |
Transients (max. 10 MHz) | ±6000 V | 5 V | ±(5% + 25 V) |
*Clamp F-1/F-2/F-3:0..3000 A (10000 Ap-p) *Clamp C-4: 0..1000 A (3600 Ap-p)*Clamp C-5: 0..1000 A (3600 Ap-p)*Clamp C-6: 0..10 A (36 Ap-p) (without current transformers) *Clamp C-7: 0…100 A (360 Ap-p )