Surge wave locator set P-900 is designed to perform the following:
When searching with an inductive method the receiver must be operated in conjunction with an additional surge wave generator, capable of producing audio frequencies of 1024±1 Hz or 2048±2 Hz, providing an output power of 200 W in a range of loads from 0.5 to 200 Ohms (for example, Audio Generator GZCH-2500).
When searching with an acoustic method the receiver must be operated in conjunction with an additional pulse generator with voltage of 10.5 – 32 kV and the energy of 150-1920 J (for example, GAUV-6).
Characteristic | Value |
Active frequencies, Hz, «1024 Hz» mode | 1024±2 |
Active frequencies, Hz, «12048 Hz» mode | 2048±2 |
Sensitivity under the maximum amplification, µV | 20 |
Sensitivity under the minimum amplification, mV | 500 |
Frequency band under -3 dB, «1024 Hz» mode | 10 |
Frequency band under -3 dB, «1024 Hz» mode | 12 |
Frequency band in the acoustic mode, Hz | 20…2200 |
Built-in battery parameters | 6 V, 2500 Ah |
Continuous duty cycle, h, min | 16 |
Package Contents
Component | Quantity |
Receiver P-900 | 1 |
Power supply | 1 |
Carrying and transportation bag | 1 |
Induction sensor | 1 |
Acoustic sensor | 1 |
Headphones | 1 |
Documentation | |
User’s Manual | 1 |