The Sonel MRU-30 uses most known methods of earth resistance measurements. Tests can be performed using the 3-pole, 4-pole, 3-pole with auxiliary clamp and also, additionally, the MRU-30 employs the two clamp method of measurement, without the use of auxiliary test rods which can’t be used in some situations. Complementary features of the MRU-30 are measurements of soil resistivity, continuity measurement of protective and equipotential conductors and, using clamps, leakage currents and interference voltages.
It allows to take the measurements of:
Additionally:
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(10% m.v. + 1 digit) |
Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC 61557-4:2007: 0,13 Ω…1999 Ω
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…1999 Ω | 1 Ω |
• measurement current: under short circuit >200mA
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (dla 50 V)
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(3% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200,0…1999 Ω | 1 Ω | ±5% m.v. |
2000…9999 Ω | 1 Ω | ±8% m.v. |
• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz).
Measurement of multiple earthing esistance with using the clamp and auxiliary electrodes (3p + clamp)
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(3% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200…1999 Ω | 1 Ω | ±5% m.v. |
2000…9999 Ω | 1 Ω | ±8% m.v. |
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• measurement current: under short circuit >20 mA,
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of resistance of auxiliary electrodes RH i RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±(5% m.v.+ 8 digits) |
1,00k…9,99 kΩ | 0,01 kΩ | |
10,0k…19,9 kΩ | 0,1 kΩ |
Measurement of multiple earthing resistance with using double clamps
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(10% m.v. + 8 digits) |
20,0…99,9 Ω | 0,1 Ω | ±(20% m.v. + 3 digits) |
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz
(for networks 60 Hz)
Measurement of ground resistivity
Measurement method: Wenner, ρ=2πLRE
Range | Resolution | Accuracy |
0,00…9,99 Ωm | 0,01 Ωm | depending on measurement accuracy RE with 4p method, but not less than ±1 digit |
10,0…99,9 Ωm | 0,1 Ωm | |
100…999 Ωm | 1 Ωm | |
1,00…9,99 kΩm | 0,01 kΩm | |
10,0…99,9 kΩm | 0,1 kΩm | |
100…999 kΩm | 1 kΩm |
L – distance between probes: 1…50 m.. or 1…150 ft
Electric security:
Rated operational conditions:
Other technical data: