Testing RCD breakers of AC, A and B types.
AC voltage and frequency measurement.
PE lead connection check using a touch electrode.
Bulit-in memory for up to 990 cels of measurement results.
Wireless radio communication interface.
Professional software for reading data and creating reports.
RCD trigger test and response time measurement tA
Measurement range according to IEC 61557: 0 ms…the upper limit of the displayed value
RCD type | Rated Current Multiplication Factor | Range | Resolution | Accuracy |
General or short delay | 0,5*IΔn | 0…300 ms | 1 ms | ±(2% m.v. + 2 digits)* |
1*IΔn | ||||
2*IΔn | 0…150 ms | |||
5*IΔn | 0…40 ms | |||
Selective | 0,5*IΔn | 0…500 ms | ||
1*IΔn | ||||
2*IΔn | 0…200 ms | |||
5*IΔn | 0…150 ms |
*for IΔn= 10 mA and 0,5 IΔn accuracy is ±2% m.v. + 3 digits
RCD disconnecting current measurement for a sine AC test current (IA)
Measurement range according to IEC 61557: (0,3…1,0)IΔn
Selected rated RCD current | Range | Resolution | Measurement current | Accuracy |
10 mA | 3,3…10,0 mA | 0,1 mA | 0,3 mA x IΔn …1,0 mA x IΔn | ±5% IΔn |
30 mA | 9,0…30,0 mA | |||
100 mA | 33…100 mA | 1 mA | ||
300 mA | 90…300 mA | |||
500 mA | 150…500 mA |
RCD disconnecting current measurement for unidirectional pulsed residual current and unidirectional pulsed current with a 6 mA DC offset (IA)
Measurement range according to IEC61557: (0,15…1,4) IΔn for IΔn > 30 mA and (0,15…2)IΔn for IΔn=10 mA
Selected rated RCD current | Range | Resolution | Measurement current | Accuracy |
10 mA | 1,5…20,0 mA | 0,1 mA | 0,15 x IΔn …2,0 mA x IΔn | ±10% IΔn |
30 mA | 4,5…42,0 mA | |||
100 mA | 15…140 mA | 1 mA | 0,15 mA x IΔn …1,4 mA x IΔn | ±10% IΔn |
300 mA | 45…420 mA |
RCD response time measurement for the residual DC current (IA)
Measurement range according to IEC61557: (0,2…2)IΔn
Selected rated RCD current | Range | Resolution | Measurement current | Accuracy |
10 mA | 2…20,0 mA | 0,1 mA | 0.2 mA x IΔn …2,0 mA x IΔn | ±10% IΔn |
30 mA | 6…60 mA | 1 mA | ||
100 mA | 20…200 mA | |||
300 mA | 60…600 mA |
IΔn – rated residual current value RCD
Touch voltage measurement referred to the rated residual current (UB)
Measurement range according to IEC61557: 10,0…99,9 V
Range | Resolution | Measurement current | Accuracy |
0…9,9 V | 0,1 | 0,4 x IΔn | 0…10% IΔn m.v. ± 5 digits |
10,0…99,9 V | 0…15% IΔn m.v. |
Earthing resistance measurement (RE)
Selected rated RCD current | Range | Resolution | Measurement current | Accuracy |
10 mA | 0,01…5,00 kΩ | 0,01 kΩ | 4 mA | 0…+10% m.v. ± 5 digits |
30 mA | 0,01…1,66 kΩ | 12 mA | 0…+10% m.v. ± 5 digits | |
100 mA | 1…5000 Ω | 1 Ω | 40 mA | 0…+5%m.v. ± 5 digits |
300 mA | 1…166 Ω | 120 mA | ||
500 mA | 1…100 Ω | 200 mA |
Voltage measurement
Measurement range in accordance with IEC 61557: 1,1 Ω…1,99 kΩ
Range | Resolution | Accuracy |
0,00…299,9 V | 0,1 V | ±(2% m.v. + 6 digits) |
300…500 V | 1 V | ±(2% m.v. + 2 digits) |
Range | Resolution | Accuracy |
45,0…65,0 Hz | 0,1 Hz | ±(0,1% m.v. + 1 digit) |
Electric security:
Other technical data:
Rated operational conditions:
„m.v.” – measured value.
mrp-201-safenergy-i-din-moxa-ti-vit-nam