INSULATION RESISTANCE MEASUREMENT UP TO 2 TΩ IN ACCORDANCE WITH IEC 61557 – 2
FULL CAPTURE AND RECORDING OF MEASUREMENT CONDITIONS
Insulation resistance measurement:
Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557 – 4 with current > 200 mA.
Circuit continuity and resistance measurement at low voltage.
Measurement of leakage current during insulation resistance testing.
Measurement of capacity during the measurement of RISO.
Continuous measurement of surrounding temperature with the capability of recording results in memory.
DC and AC voltage measurement in the range of 0-600 V.
990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR-1 adapter) or through a USB cable.
Electrical safety:
Other technical specifications:
Insulation resistance measurement (two-lead)
Measurement range acc. to IEC 61557 – 2 for RISOmin=UISOnom/IISOmax…2 TΩ (IISOmax=1 mA)
Range | Resolution | Accuracy |
0,0…999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 20 digits) |
1,000…9,999 MΩ | 0,001 MΩ | |
10,00…99,99 MΩ | 0,01 MΩ | |
100,0…999,9 MΩ | 0,1 MΩ | |
1,000…9,999 GΩ | 0,001 GΩ | |
10,00…99,99 GΩ | 0,01 GΩ | |
100,0…999,9 GΩ | 0,1 GΩ | |
1,000…2,000 TΩ | 0,001 TΩ |
Values of measured resistance depending on measurement voltage
Voltage UISO | Measurement range |
50 V | 50 GΩ |
100 V | 100 GΩ |
250 V | 250 GΩ |
500 V | 500 GΩ |
1000 V | 1,00 TΩ |
2500 V | 2,00 TΩ |
Measurement of insulation resistance with the AutoISO-2500 adapter
Range | Resolution | Accuracy |
0,0…999.9 kΩ | 0,1 Ω | ±(3% m.v. + 20 digits) of the meter + max 1% of AutoISO-2500 uncertainty |
1,000…9.999 MΩ | 0,001 MΩ | |
10,00…99,99 MΩ | 0,01 MΩ | |
100,0…999,9 MΩ | 0,1 MΩ | |
1,000…9,999 GΩ | 0,001 GΩ | |
10,00…99,99 GΩ | 0,01 GΩ | |
100,0…400,0 GΩ | 0,1 GΩ | ±(3% m.v. + 20 digits) of the meter + max 5% of AutoISO-2500 uncertainty |
Values of measured resistance depending on measurement voltage
Voltage UISO | Measurement range |
100 V | 100 GΩ |
250 V | 250 GΩ |
500 V, 1000 V, 2500 V | 400 GΩ |
Continuity measurement of protective connections and equipotential bonding with 200 mA current
Measurement range acc. to EN 61557 – 4: 0.10…999 Ω
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200…999 Ω | 1 Ω | ±(4% m.v. + 3 digits) |
Resistance measurement with low current
Range | Resolution | Accuracy |
0,0…199,9 Ω | 0,1 Ω | ±(2% m.v. + 3 digits) |
200…999 Ω | 1 Ω | ±(4% m.v. + 4 digits) |
Capacity measurement
Display range | Resolution | Accuracy |
1…999 nF | 1 nF | ±(5% m.v. + 10 digits) |
1,00…9,99µF | 0,01µF |
Temperature measurement
Range | Resolution | Accuracy |
-40,0…99,9°C | 0,1°C | ±(3% m.v. + 8 digits) |
-40,0…221,8°F | 0,1°F | ±(3% m.v. + 16 digits) |
DC and AC voltage measurement
Range | Resolution | Accuracy |
0…600 V | 1 V | ±(3% m.v. + 2 digits) |
Frequency range : 45…65 Hz