I/O Modules for ioPAC 8600 series modular programmable controllers
| CPU10 Series Specifications | |
| • Computer | |
| CPU Type | 32-bit ARM9 192 MHz CPU |
| OS | Linux |
| Clock | Real-time clock with super capacitor (retains charge for 7 days) |
| • Memory | |
| SDRAM | 64 MB |
| Flash | 32 MB (10 MB reserved for user) |
| FRAM | 128 KB |
| microSD™ Slot | Up to 32 GB (SD 2.0 compatible) Note: For units operating in extreme temperatures, industrial-grade, wide-temperature microSD cards are required. |
| • Switches & Buttons | |
| Rotary Switch | 0 to 9 |
| Button | Reset to factory defaults |
| • Ethernet Interface | |
| LAN | 2 x 10/100 Mbps, Ethernet bypass or 2 MACs (IPs), jumper selectable, RJ45 or M12 |
| Protection | 1.5 kV magnetic isolation |
| Automation Languages | C/C++ or IEC 61131-3 |
| Protocols | Modbus TCP/RTU (master/slave), SNMP, TCP/IP, UDP, DHCP, BOOTP, SNTP, SMTP |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 200 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 1,032,466 hrs |
| Standard | Telcordia SR332 |
| PW10-15W-T Specifications | |
| • Power | |
| Input Voltage | 24 to 110 VDC (16.8 to 154 VDC) Note: Compliant with EN 50155 at 24/48/60/72/110 VDC |
| Wattage | 15 W |
| Galvanic Isolation | 3k VDC |
| Dual-Power Input | Yes |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • MTBF (mean time between failures) | |
| Time | 1,579,517 hrs |
| Standard | Telcordia SR332 |
| 86M-1832D-T Specifications | |
| • Inputs and Outputs | |
| Digital Inputs | 8 channels |
| Isolation | To system: 3k VDC or 2k Vrms Channel-to-channel: 1k VDC |
| • Digital Input | |
| Sensor Type | Wet contact (NPN or PNP) |
| I/O Mode | DI, counter, or frequency |
| Wet Contact (DI+ to DI-) | • On: 10 to 30 VDC • Off: 0 to 3 VDC |
| Counter Frequency | 5 kHz |
| Digital Filtering Time Interval | Software selectable (by 0.1 ms) |
| • Physical Characteristics | |
| Wiring | I/O cable, 16 AWG (max.) |
| Connector | Spring-type terminal block |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 12.6 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 1,149,108 hrs |
| Standard | Telcordia SR332 |
| 86M-2830D-T Specifications | |
| • Inputs and Outputs | |
| Digital Outputs | 8 channels |
| Isolation | To system: 3k VDC or 2k Vrms Channel-to-channel: 1k VDC |
| • Digital Output | |
| Type | Sink |
| I/O Mode | DO or PWM |
| Pulse Output Frequency | 1 kHz |
| Short Circuit Protection | 750 mA @ 25°C |
| Over-Voltage Protection | 41 VDC |
| Over-Current Protection | 2.6 A (4 channels @ 650 mA) |
| Over-Temperature Shutdown | 175°C (typical), 150°C (min.) |
| Current Rating | 200 mA per channel |
| • Physical Characteristics | |
| Wiring | I/O cable, 16 AWG (max.) |
| Connector | Spring-type terminal block |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 76.7 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 1,766,037 hrs |
| Standard | Telcordia SR332 |
| 86M-2604D-T Specifications | |
| • Inputs and Outputs | |
| Relays | 6 channels |
| Isolation | To System: 3k VDC or 2k Vrms |
| • Relay | |
| Type | Form A (N.O.) |
| I/O mode | DO or PWM |
| Pulse Output Frequency | 0.33 Hz |
| Contact Current Rating | Resistive Load: 5 A @ 30 VDC, 250 VAC |
| Relay On/Off Time | 10 ms (max.) |
| Initial Insulation Resistance | 1000 mega-ohms (min.) @ 500 VDC |
| Mechanical Endurance | 5,000,000 operations |
| Electrical Endurance | 60,000 operations @ 5 A resistive load |
| Contact Resistance | 100 milli-ohms (max.) |
| • Physical Characteristics | |
| Wiring | I/O cable, 16 AWG (max.) |
| Connector | Spring-type terminal block |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 127 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 4,173,843 hrs |
| Standard | Telcordia SR332 |
| 86M-4420-T Specifications | |
| • Inputs and Outputs | |
| Analog Outputs | 4 channels |
| Isolation | To system: 3k VDC or 2k Vrms |
| • Analog Output | |
| Resolution | 12 bits |
| Output range | 0 to 10 V, -10 to 10 V, 0 to 20 mA, 4 to 20 mA |
| I/O mode | Static or Waveform mode |
| Voltage Output | 10 mA (max.) |
| Accuracy | ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C |
| Current Load Resistance | Internal Power: 400 ohms External 24 VDC Power: 1000 ohms |
| Update Rate | Software polling or waveform mode |
| Waveform Type | Sine, Triangle, Square |
| Wavemode Frequency | 125 Hz |
| • Physical Characteristics | |
| Wiring | I/O cable, 16 AWG (max.) |
| Connector | Spring-type terminal block |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 94.2 mA @ 24 VDC (voltage) 143.8 mA @ 24 VDC (current) |
| • MTBF (mean time between failures) | |
| Time | 2,409,345 hrs |
| Standard | Telcordia SR332 |
| 86M-1620D-T Specifications | |
| • Inputs and Outputs | |
| Digital Inputs | 16 channels |
| Isolation | To system: 3k VDC or 2k Vrms |
| • Digital Input | |
| Type | PNP |
| I/O mode | DI |
| Logic Definition | • On: channel voltage > 0.3 x (external power voltage) • Off: channel voltage < 0.15 x (external power voltage) |
| Scan Period | 8 ms (typ.) |
| Scan on Time | 0.5 ms |
| Debouncing Function | Software disable/enable |
| Debouncing Time | 1 to 15 ms (software-selectable) |
| Common Type | 8 points per COM |
| • Physical Characteristics | |
| Wiring | I/O cable, 16 AWG (max.) |
| Connector | Spring-type terminal block |
| Channel LED | Yes |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 12.6 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 1,115,244 hrs |
| Standard | Telcordia SR332 |
| 86M-5212U-T Specifications | |
| • Ethernet Communication | |
| Interface | Two 2-wire Ethernet ports |
| Isolation | To system: 3k VDC or 2k Vrms |
| • Standards | |
| Supported Standards | 100BASE-TX IEEE 802.3u 10BASE-T IEEE 802.3 100 Mbps BroadR-Reach® 10 Mbps BroadR-Reach® |
| • Physical Characteristics | |
| Wiring | CAT 5 standard cable with M12 D-code male connection |
| Connector | M12 (D-code, female) x 2 |
| Channel LED | Yes |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 578 mA @ 3.3 VDC |
| • MTBF (mean time between failures) | |
| Time | 2,498,942 hrs |
| Standard | Telcordia SR332 |
| 86M-5250-T Specifications | |
| • Serial Communication | |
| Interface | 2 CAN ports |
| Isolation | To system: 3k VDC or 2k Vrms |
| • CAN Bus Communication | |
| Protocols | CAN 2.0A CAN 2.0B CANopen DS301, V4.02 CANopen DS401 |
| Speed | 10/20/50/125/250/500/800 kbps, 1 Mbps |
| Termination Resistor | N/A, 120 ohms (by DIP) |
| • Physical Characteristics | |
| Connector | DB9 male |
| Channel LED | Yes |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| • Power Requirements | |
| Input Current | 60 mA @ 24 VDC |
| • MTBF (mean time between failures) | |
| Time | 3,306,609 hrs |
| Standard | Telcordia SR332 |
| Common Specifications | |
| • Power Requirements | |
| Input Voltage | 24 to 110 VDC (16.8 to 154 VDC) |
| • Environmental Limits | |
| Operating Temperature | -40 to 75°C (-40 to 176°F) |
| Storage Temperature | -40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity | 5 to 95% (non-condensing) |
| Shock | IEC 60068-2-27 |
| Vibration | IEC 60068-2-6 |
| • Standards and Certifications | |
| Safety | UL 508 |
| EMC | EN 55032/24 |
| EMI | FCC Part 15 Subpart B Class A, CISPR 32 |
| EMS | IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1000 MHz: 3 V/m 1400 MHz to 2100 MHz: 3 V/m 2100 MHz to 2700 MHz: 1 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L); |
| Rail Traffic | EN 50155 (essential compliance*), EN 50121-3-2, EN 50121-4 *Moxa defines “essential compliance” to include those EN 50155 requirements that make products more suitable for rolling stock railway applications. |
| • Warranty | |
| Warranty Period | 5 years |
| Details | See www.moxa.com/warranty |
| Model No. | Description | |
|---|---|---|
| 86M-1620D-T | 16 DIs, sink, 24 to 110 VDC, channel LED, -40 to 75°C operating temperature | |
| 86M-1832D-T | 8 DIs, sink/source, 24 VDC, ch-to-ch isolation, channel LED, -40 to 75°C operating temperature | |
| 86M-2604D-T | 6 relays, form A (N.O.), channel LED, -40 to 75°C operating temperature | |
| 86M-2830D-T | 8 DOs, sink, 24 VDC, ch-to-ch isolation, channel LED, -40 to 75°C operating temperature | |
| 86M-4420-T | 4 AOs, 0 to 10 V, -10 to 10 V, 0 to 20 mA, or 4 to 20 mA, -40 to 75°C operating temperature | |
| 86M-5212U-T | 2-port 2-wire Ethernet switch, -40 to 75°C operating temperature | |
| 86M-5250-T | 2 CAN ports, -40 to 75°C operating temperature |

iopac-8600-series-expansion-modules-safenergy-i-din-moxa-ti-vit-nam